The ISE/ West 6010Plusis a 1/16 DIN microprocessor based digital indicator. Available with red or green displays. Fixed red display is standard while other display colors could delay shipment by up to 2 weeks. Up to 4 outputs are available. The digital indicator can be reconfigured with available plug-in modules.
· Four-digit LED display
· Engineering units
· Up to 4 alarms
· PC configuration
· Transmitter power supply option
· PV retransmit option
· Min/max value hold
· RS485 comms option


Features
Output Configuration Up to 4 total., max 4 for Alarms, max 2 triac outputs, max 3 for retransmit of PV, max 1 transmitter power supply
Alarm 1- 4 Types Process high, process low, direct acting, process high, process low reverse and logical OR. Latching function is available on all alarms
Viewable Values Process variable, maximum value, minimum value and elapsed time since reset
Human Interface 3 button operation, 4 digit 10mm high red or green display, plus set-up, alarm, max & min indicators
PC Configuration Off-line configuration from serial port to dedicated configuration socket (comms option not required)
Input
Thermocouple - J, K, R, S, T, B, L, C, Pt-Rh20% vs Pt-Rh40% & N.
RTD - 3 Wire PT100, 50ohm per lead maximum (balanced).
DC Linear - 0-20/4-20mA, 0-50/10-50mV, 0-5/1-5/0-10/2-10V. Scaleable -1999 to 9999, decimal point selectable.
Impedance - >10Mohm for Thermocouple and mV ranges, 47Kohm for V ranges and 5ohm for mA ranges.
Accuracy - +/- 0.1% of input span +/- 1 LSD (T/C CJC better than 1°C).
Sampling - 4 per second, 14 bit resolution.
Sensor Break Detection - <2 secs (except zero based DC ranges), control O/P's turn off, high alarms activate for T/C and mV ranges, low alarms activate for RTD, mA or V ranges.
Outputs & Options
Single Relay OutputContacts SPDT 2 Amp resistive at 240V AC, >500,000 operations, latching or non-latching. (3 maximum in control)
DualRelay Output Contacts DPST 2 Amp resistive at 240V AC,>200,000 operations. (May be fitted in output 2 or 3 only)
Retransmit Output 0-20/4-20mA into 500 ohm max, 0-10/0-5V into 500 ohm min. Accuracy: +/- 0.25%
Transmitter PowerSupply 20-28V DC (24V nominal), min load 910 ohm
Digital Inputs External reset of latching alarm 1 relay. Volt free or TTL input (Reset = open to close or "0" to "1" transition. 0 = -0.6 to 0.8V, 1 = 2 to 24V); Can be used to reset latched alarms or set tare.
Communications 2 wire RS485, 1200 to 19200 baud. Modbus or West ASCII (selectable)
General
Temperature & RH 0 to 55°C (-20 to 80°C storage), 20% to 95%RH non-condensing
Power Supply 90 to 264V 50/60Hz (optional 20 to 55V AC/22 to 65V DC), approx 4 Watts
Front Panel Protection IEC IP66 (Behind panel protection is IP20)
Approvals andCertification CE, UL & ULc