Most Configurations Are In
Stock For Same Day Shipment
We will advise immediately if your order will be delayed
The ISE/
West 8010
Plus is a 1/8 DIN microprocessor based digital
indicator. Available with red, green or changeable
red & green
displays. Fixed red display is standard while other display colors could delay
shipment by up to 2 weeks. Up to 5 outputs are available. The digital indicator
can be reconfigured with available plug-in modules.
· Four-digit
LED display
· Engineering
units
· Up
to 5 alarms
· PC
configuration
· Transmitter
power supply option
· PV
retransmit option
· Min/max
value hold
· RS485
comms option



Features Output Configuration
Up to 5 total., max 5 for Alarms, max 2 triac outputs, max 3 for retransmit of PV, max 1 transmitter
power supply
Alarm 1- 5
Types Process high, process low, direct acting, process high, process
low reverse and logical OR. Latching function is available on all alarms
Viewable Values
Process variable, maximum value, minimum value and elapsed time since reset
Legends
°C/°F LED.
Human Interface
3 button operation, 4 digit 13mm high red or green display, plus set-up, alarm,
max & min indicators
PC Configuration
Off-line configuration from serial port to dedicated configuration socket (comms option
not required)
Input
Thermocouple - J, K, R, S, T, B, L,
C, Pt-Rh20% vs Pt-Rh40% & N.
RTD - 3 Wire PT100, 50ohm per lead maximum (balanced).
DC Linear - 0-20/4-20mA, 0-50/10-50mV, 0-5/1-5/0-10/2-10V. Scaleable
-1999 to 9999, decimal point selectable.
Impedance - >10Mohm for Thermocouple and mV ranges, 47Kohm for V
ranges and 5ohm for mA ranges.
Accuracy - +/- 0.1% of input span +/- 1 LSD (T/C CJC better than
1°C).
Sampling - 4 per second, 14 bit resolution.
Sensor Break Detection - <2 secs (except zero based DC ranges),
control O/P's turn off, high alarms activate for T/C and mV ranges, low
alarms activate for RTD, mA or V ranges.
Outputs
& Options
Single Relay Output
Contacts SPDT 2 Amp resistive at 240V AC, >500,000 operations,
latching or non-latching. (3 maximum in control)
Dual
Relay Output Contacts SPST 2 Amp resistive at 240V AC,>200,000 operations.
(May be fitted in output 2 or 3 only)
Retransmit Output
0-20/4-20mA into 500 ohm max, 0-10/0-5V into 500 ohm min. Accuracy: +/- 0.25%
Transmitter Power
Supply 20-28V DC (24V nominal), min load 910 ohm
Digital Inputs
External
reset of latching alarm 1 relay. Volt free or TTL input (Reset = open to close
or "0" to "1" transition. 0 = -0.6 to 0.8V, 1 = 2 to 24V); Can be used to
reset latched alarms or set tare.
Communications 2
wire RS485, 1200 to 19200 baud. Modbus or West ASCII (selectable)
General
Temperature & RH
0 to 55°C (-20 to 80°C storage), 20% to 95%RH non-condensing
Power Supply
90 to 264V 50/60Hz (optional 20 to 55V AC/22 to 65V DC), approx 4 Watts
Front Panel
Protection IEC IP66 (Behind panel protection is IP20)
Approvals and
Certification CE, UL & ULc